#!/usr/bin/env python3
from lib60870 import *
import time
class IEC60870_5_104_client:
# Connection event handler
def connectionHandler (self, parameter, connection, event):
if event == CS104_CONNECTION_OPENED:
print("Connection established")
elif event == CS104_CONNECTION_CLOSED:
print("Connection closed")
elif event == CS104_CONNECTION_STARTDT_CON_RECEIVED:
print("Received STARTDT_CON")
elif event == CS104_CONNECTION_STOPDT_CON_RECEIVED:
print("Received STOPDT_CON")
#CS101_ASDUReceivedHandler implementation
#For CS104 the address parameter has to be ignored
def asduReceivedHandler (self, parameter, address, asdu):
print("RECVD ASDU type: %s(%i) elements: %i" % (
TypeID_toString(CS101_ASDU_getTypeID(asdu)),
CS101_ASDU_getTypeID(asdu),
CS101_ASDU_getNumberOfElements(asdu)))
if (CS101_ASDU_getTypeID(asdu) == M_ME_TE_1):
print(" measured scaled values with CP56Time2a timestamp:")
for i in range(CS101_ASDU_getNumberOfElements(asdu)):
io = cast(CS101_ASDU_getElement(asdu, i), MeasuredValueScaledWithCP56Time2a)
print(" IOA: %i value: %i" % (
InformationObject_getObjectAddress(cast(io, InformationObject) ),
MeasuredValueScaled_getValue(cast(io, MeasuredValueScaled) )
))
MeasuredValueScaledWithCP56Time2a_destroy(io)
elif (CS101_ASDU_getTypeID(asdu) == M_SP_NA_1):
print(" single point information:")
for i in range(CS101_ASDU_getNumberOfElements(asdu)):
io = cast(CS101_ASDU_getElement(asdu, i), SinglePointInformation)
print(" IOA: %i value: %i" % (
InformationObject_getObjectAddress(cast(io,InformationObject) ),
SinglePointInformation_getValue(cast(io,SinglePointInformation) )
))
SinglePointInformation_destroy(io)
elif (CS101_ASDU_getTypeID(asdu) == M_DP_NA_1):
print(" double point information:")
for i in range(CS101_ASDU_getNumberOfElements(asdu)):
io = cast(CS101_ASDU_getElement(asdu, i), DoublePointInformation)
print(" IOA: %i value: %i" % (
InformationObject_getObjectAddress(cast(io,InformationObject) ),
DoublePointInformation_getValue(cast(io,DoublePointInformation) )
))
DoublePointInformation_destroy(io)
elif (CS101_ASDU_getTypeID(asdu) == M_ME_NB_1):
print(" measured value scaled:")
for i in range(CS101_ASDU_getNumberOfElements(asdu)):
io = cast(CS101_ASDU_getElement(asdu, i), MeasuredValueScaled)
print(" IOA: %i value: %i" % (
InformationObject_getObjectAddress(cast(io,InformationObject) ),
MeasuredValueScaled_getValue(cast(io,MeasuredValueScaled) )
))
MeasuredValueScaled_destroy(io)
elif (CS101_ASDU_getTypeID(asdu) == C_SC_NA_1):
print("received single command response")
for i in range(CS101_ASDU_getNumberOfElements(asdu)):
io = cast(CS101_ASDU_getElement(asdu, i), SinglePointInformation)
print(" IOA: %i value: %i" % (
InformationObject_getObjectAddress(cast(io,InformationObject) ),
SinglePointInformation_getValue(cast(io,SinglePointInformation) )
))
SinglePointInformation_destroy(io)
elif (CS101_ASDU_getTypeID(asdu) == C_DC_NA_1):
print("received double command response")
for i in range(CS101_ASDU_getNumberOfElements(asdu)):
io = cast(CS101_ASDU_getElement(asdu, i), DoublePointInformation)
print(" IOA: %i value: %i" % (
InformationObject_getObjectAddress(cast(io,InformationObject) ),
DoublePointInformation_getValue(cast(io,DoublePointInformation) )
))
DoublePointInformation_destroy(io)
return True
def __init__(self, ip = "localhost", port = IEC_60870_5_104_DEFAULT_PORT):
print("Connecting to: %s:%i" % ( ip, port))
self.con = CS104_Connection_create(ip, port)
self.p_connectionHandler = CS104_ConnectionHandler(self.connectionHandler)
self.p_asduReceivedHandler = CS101_ASDUReceivedHandler(self.asduReceivedHandler)
CS104_Connection_setConnectionHandler(self.con, self.p_connectionHandler, None)
CS104_Connection_setASDUReceivedHandler(self.con, self.p_asduReceivedHandler, None)
def start(self):
if (CS104_Connection_connect(self.con)):
print("Connected!")
CS104_Connection_sendStartDT(self.con)
time.sleep( 5 )
CS104_Connection_sendInterrogationCommand(self.con, CS101_COT_ACTIVATION, 1, IEC60870_QOI_STATION)
time.sleep( 5 )
#sc = cast(SingleCommand_create(None, 5000, True, False, 0), InformationObject)
#print("Send control command C_SC_NA_1")
#CS104_Connection_sendProcessCommandEx(self.con, CS101_COT_ACTIVATION, 1, sc)
#InformationObject_destroy(sc)
#time.sleep( 5 )
dc = cast(DoubleCommand_create(None, 6000, 1, True, 0), InformationObject)
print("Send control command C_DC_NA_1")
CS104_Connection_sendProcessCommandEx(self.con, CS101_COT_ACTIVATION, 1, dc)
InformationObject_destroy(dc)
time.sleep( 0.5 )
dc = cast(DoubleCommand_create(None, 6000, 1, False, 0), InformationObject)
print("Send control command C_DC_NA_1")
CS104_Connection_sendProcessCommandEx(self.con, CS101_COT_ACTIVATION, 1, dc)
InformationObject_destroy(dc)
time.sleep( 5 )
# Send clock synchronization command
#newTime = sCP56Time2a()
#CP56Time2a_createFromMsTimestamp(CP56Time2a(newTime), Hal_getTimeInMs())
#print("Send time sync command")
#CS104_Connection_sendClockSyncCommand(self.con, 1, CP56Time2a(newTime))
#time.sleep( 1 )
CS104_Connection_sendStopDT(self.con)
else:
print("Connect failed!")
CS104_Connection_destroy(self.con)
print("exit")
#test the class
if __name__== "__main__":
client = IEC60870_5_104_client()
client.start()